HASIL AUDIT ENERGI DI INDUSTRI TEKSTIL

Main Article Content

Achmad Hasan

Abstract

Energy audit is one way to plan for optimizing the supply and use of energy
needed by the industry. Portrait of the use of electrical energy used in textile
industry supplied from PT.PLN (Persero) with the power contract for 23000 kVA
and POJ Power (Mini Hydro Power Plant, Jatiluhur) with installed capacity of
5800 kVA. Especially for electric energy supplied from POJ Power, status of
electricity continues to be a contract with the manager of POJ Power Jatiluhur.
Based on the results of measurement of power quality with PQA Hioki 3197 is as
described in the previous section, it can be seen that: (a) Voltage magnitude at
some of the panel is high (about 250 V), (b) The power factor is very low, (c)
Generally, voltage and current THD (Total Harmonic Distortion) is very high.
Kata kunci: energi, listrik, penghematan, filter harmonik, faktor daya